继电保护配置与整定计算

2023-06-09 06:06| 来源: 网络整理| 查看: 265

 

 

继电保护配置与整定计算

 

 

专业:电气工程及其自动化

 

 

 

摘要:

依据对电力系统继电保护的基本要求(即选择性、速动性、灵敏性和可靠性)

,并按照继

电保护的配置与整定原则,以一简单电力系统为例,阐述了电力系统继电保护配置与整定计算的完

整过程。首先,对元件参数进行计算,对进行短路电流进行计算。计算的短路类型包括单相接地短

路、两相接地短路、两相短路和三相短路。其次,根据电力系统各个要求,配置和选择相应的电流

互感器、电压互感器。第三部分,则是继电保护的配置与整定计算。发电机保护,以

25MW

的汽轮

发电机为例,按照其容量、类型等,主要配置的保护类型有差动保护、过电流保护、过负荷保护、

接地保护、失磁保护。变压器保护以变压器

SFSL1-31500

为例,配置的保护类型有差动保护、过电

流保护、过负荷保护。线路保护,

110kV

线路配置相间距离保护和零序电流保护,

35kV

线路配置相

间短路保护和接地短路保护,此外,线路均配置三相重合闸。母线保护,以双母线为例,配置完全

电流差动保护。

各种保护的整定计算,

均按照

《电力系统继电保护配置及整定计算》

中的原则方法,

计算出保护的整定值和保护的动作时限。

关键词:

电力系统;继电保护;保护;配置;整定;短路

Abstract

According to the basic demand of relay protaction of electric power system

contains 

selectivity

quike-activity

sensitivity 

and 

reliability

and 

the 

principle 

of 

its 

allocation 

and 

set,take 

simple 

power 

system 

for 

instance,presents 

complete 

process 

of 

relay 

protection

allocation 

and 

set 

calculation of power system. First,calculate the parameters of members and the short-circuit current .The 

variety 

of 

short-circuit 

contains 

single 

phase 

grounding 

double 

phases 

grounding

double 

phases 

short-circuit 

and 

three 

phases 

short-circuit. 

Second, 

allocate 

and 

select 

current 

or 

voltage 

transformers 

according 

to 

the demand 

of 

power 

system. 

Third, 

allocate 

and 

calculate 

the 

relay 

protection. 

Generator 

protection,take 

25MW 

steam 

turbine 

for 

instance,according 

to 

its 

capacity 

and 

variety,the 

allocated 

protections 

contain 

differential 

protection

overcurrent 

protection

overload 

protection

grounding 

protection

loss-of-excitation 

protection. 

Transformer 

protection,take 

transformer(SFSL1-31500)for 

instance,its protections contain differential protection

overcurrent protection

overload protection. Line 

protection, 

the 

110kv 

lines allocate 

interphase 

distance protection 

and 

zero 

sequence 

current 

protection, 

and 

35kv 

line 

allocates 

interphase 

short-circuit 

protection 

and 

grounding 

short-circuit 

protection. 

Otherwise, line protection also contains three phases reswitching. Generatrix protection, take a double bus 

for instanse, allocates complete current differential protection. All principle and methods of Every kind of 

protection and count, are based on the

 

electric power system relay protection allocate and count .

 

 

 

 

 

 

 

 

 

Keywords

Electric power system

relay protection

protection

allocate

set

short-circuit 

 

 

 