更换IM153 您所在的位置:网站首页 亲子自制书签绘本如何制作图片 更换IM153

更换IM153

#更换IM153| 来源: 网络整理| 查看: 265

问题描述

尊敬的各位专家:,

Dear all experts,

我是西门子的新手(我来自施耐德的世界)。在我的工厂,我们有一辆S7-400驾驶一些

I'm new to Siemens (I'm coming from Schneider's world). In my plant we have an S7-400 driving some

带有不同模块的IM153-1。

IM153-1 with differents modules.

因此,我的第一个测试是在IM153-1之间交换DB9 probifus连接器,错误仍然存在。

So my first test was to swap the DB9 probifus connector beetween the IM153-1, the error was still there.

在我的办公室里有一些备件(不是新的,但100%工作),所以我拿了一个IM153-1,放了相同的Profibus ID(24),并更换了工厂里的备件。。。

In my office there is some spare parts, (not new but working at 100%) so I took an IM153-1 put the same Profibus ID (24) and replace those in the plant...

现在错误是“有效结构与编程的不同”,现在我被阻止了,我不知道如何从S7-400重新发送配置。

Now the error is "Effective structure is different than those programmed" , and now I'm blocked I do not know how to resend the configuration from the S7-400.

推荐答案2

你好Emmerson Fonito,

Hello Emmerson Fonito,

当您遇到任何问题时,应该始终读取CPU的事件缓冲区。你在那里得到的信息更加详细。

when you have any problems you should always read event buffer of your CPU. The information you get there is more detailled.

当您更换部件时,您必须记住硬件配置是特定于部件的。尤其是当你用较新的模块替换较旧的模块时,你很可能会遇到问题。

When you exchange parts, you have to keep in mind that HW-configuration is part specific. Especially when you change a newer against an older module you are likely to experiance problems.

现在,您必须将已更改模块的硬件配置更改为您已下载的配置。或者,根据您的模块,您可以检查是否可以通过下载不同的固件将模块升级到更新版本。您可以在硬件目录中检查那里的模块和替换模块之间的差异。

Now you will either have to change HW-configuration for changed module to what you have put there an download. Or, depending on your module, you could check if you can upgrade your module to newer by downloading different firmware. You can check in HW-catalog what the differences between the modul there and the replacement module are.

您是否已尝试更改回原始模块?如果是,错误是否仍然继续?

Did you already try to change back to original module? If yes, did error still resume?

如果您有足够的备件,您还可以创建一个小型测试项目,在该项目中集成更改的IM 153-1,进行硬件配置,然后查看测试项目中是否也会出现错误,以确保它确实是模块。

If you have enough spare parts, you could also create a small test project where you integrate the changed IM 153-1, do the HW-configuration and then see if error would be in test project too - to be sure its really the module.

当做

regards

推荐答案3

谢谢你的回答,星期三我会回到这个工厂,我会尝试一个小项目,我还有一个S7-400

Thank you for your answer, I'll back to this plant wednesday, I'll try a small project, I have another S7-400

推荐答案4

非常感谢,我尝试用同样错误的原始模块替换模块。

Thanks a lot, I try to replace the module with the original one with the same error.

我在想,我在替换模块的过程中(用相同的部件#)是完全错误的,是否有一个完整的教程来做这件事?

I'm thinking that I'm totally wrong in the procedure to replace the module (by the same part #), is there anyway a complete tutorial for doing that?

非常感谢你的帮助

Thanks a lot for your help

埃默森

Emmerson

推荐答案5

您是否将Profibus地址设置为与旧模块相同?关于更换,我们没有什么特别之处。关闭电源,更换模块并打开电源。。。

Did you set the Profibus address the same as in the old module? There us nothing special regarding replacement. Switsh off the power, replace the module and power on...

两个模块的MLFB编号是否相同?(6ES7 151。。。

Are the MLFB number of both modules the same? (6ES7 151...

推荐答案6

感谢您的帮助,

Thank you for your help,

Sure I set the same profibus address (24) by setting the same dip switch.

我的两个模块共享相同的代码:6ES7 153-1AA03-0XB0

My two modules share the same code: 6ES7 153-1AA03-0XB0

这是我的主要硬件配置屏幕,除了#24所有关闭的Profibus主机是正常的,因为它们由主程序打开。

This is my main HW Config screen, except the #24 all off Profibus host are normal since they are switch on by the main program.

推荐答案7

如果有人能帮我的话,请给我一点小费。

Just a small up if someone can help me.

推荐答案8

发布的新问题RaviS 与主题分离为一个单独的线程更换模块IM-151.

New question published byRaviS is split to a separate thread with the subject Change module IM-151 .

致以最诚挚的问候Min_Moderator

Best regardsMin_Moderator

推荐答案9

嘿emmerson,

hey emmerson,

你现在在哪?让你以前的im重新参与这个项目?

at which point are you at the moment? got your old im back in the project?

回想一下:您的项目已经工作了两周,然后出现了通信错误。

to summon it up: you had working project for two weeks, then a communication error occurs.

是否可以通过重新启动plc来克服错误?

Was it possible to get over the error by restarting the plc?

发生错误之前的一些更改在哪里?

Where some changes before the error occured?

关于更换:im153-1的固件版本是否相同?如果插入FW低于预测值的模块,则会收到“不同模块”警告。

regarding the replacement: had both im153-1 the same firmware version? you will get the "different modules" warning if you insert a modul with lower FW than projected.